Wireless sensors and Yggio, the open operational layer for cities, property owners and transport operators. Your data, your operations, your sovereignty.

LoRaWAN Quick start

Strips Comfort for LoRaWAN: quick start

From the opened box to a working sensor on one page. The full manual has the details, the settings and the troubleshooting.

Revision B · November 2026 · Sensative AB

Strips Comfort measures temperature, relative humidity and ambient light (lux) where it is mounted, and reports them over LoRaWAN.

In the box

  • Strips Comfort, with the adhesive already on the back
  • One or two magnets on the sensor. They keep it in transport mode. Keep one for magnet commands.
  • The LoRaWAN keys (DevEUI, JoinEUI and AppKey), on a label in the box and by e-mail

You need

  • A LoRaWAN gateway within range, powered on and online
  • An account on a LoRaWAN network server, with the gateway added
  • The region on the sensor's label. Gateway and network server must use the same region, and in US915 and AU915 the same sub-band.
  • The Strips payload decoder in your network server or application
  • Optional: the Strips LoRa Config Tool, only if you want to change the configuration

From box to ready

1

Register the sensor in the network server

Add a new end device: OTAA, LoRaWAN 1.0.4, regional parameters RP002-1.0.1 and the frequency plan for your region. Enter the DevEUI, JoinEUI (AppEUI) and AppKey exactly, and add the Strips payload decoder.

Done when: the device is listed, waiting for its first join.
2

Join and check the signal

Take every magnet off the sensor. It sends a join request, shown by one long green blink, and gives another long green blink when joined. If the magnets have already been off, start the join with the magnet instead: three times to the rounded end, and a short orange blink shows the join request. Five short red blinks means the join failed: check the keys, region, sub-band and gateway. Then hold Strips where it will sit and send an uplink: magnet to the rounded end three times, 20 cm away and 2 seconds apart.

Done when: the network server shows the device as joined, and the link carries at least SF9 (SNR above −5 dB, RSSI above −115 dBm).
3

Check what it reports

Strips Comfort is delivered configured: it sends the average temperature, the humidity and the light once an hour, with the battery level, and a heartbeat once a day. To change that, choose Strips Multi-sensor +Comfort and a profile in the Strips LoRa Config Tool, send the payload as a downlink on port 11, then send an uplink with the magnet so that Strips picks it up.

Done when: the first hourly report arrives, or, after a new profile, Strips answers with status code 0300 (OK).
4

Choose the place and mount

For room climate: an inside wall, away from direct sun, radiators, other heat sources and draughts. For light: where the light falls as in the rest of the room, not behind curtains or inside cupboards. Indoors, or outdoors in a sheltered spot out of rain and standing water (IP63). Clean the surface (clean, dry, at least +10 °C), peel the film off the adhesive and press Strips firmly in place.

Strips Comfort on an inside wall, away from a sunny window and a radiator
An inside wall, away from the window and the radiator.
Do not mount Strips on metal. The adhesive is permanent, so check the position first.
5

Test

Check that the first values are plausible for the room. Breathe on the sensor or cover it with your hand to see humidity and light change.

Done when: temperature, humidity and light arrive in your application.

More in the full manual

Settings, troubleshooting, maintenance and specifications are in the Strips Comfort for LoRaWAN manual.

Support: support@sensative.com